12 Volt Wire Size Chart

Minimum copper cable size (AWG) by current and one-way distance, at 3% voltage drop.

Current3 ftone way5 ftone way10 ftone way15 ftone way20 ftone way25 ftone way
5 A161614121210
10 A1614121088
15 A141210866
20 A14128664
30 A12106442
40 A1086422
50 A1084221/0
60 A106421/01/0
80 A8621/01/02/0
100 A6421/02/03/0
125 A441/02/03/04/0
150 A421/03/04/0—
200 A222/04/0——
250 A1/01/03/0———
300 A2/02/04/0———

Sizes are for copper cable on a 12-volt circuit. — means no single cable up to 4/0 will do: shorten the run, use a higher voltage, or run two cables in parallel.

How to read the chart

  1. Find your currentAmps = watts ÷ volts. For an inverter, use its watts ÷ 10, which allows for the inverter’s losses.
  2. Measure one wayUse the distance from the battery to the load, not the round trip — the chart already allows for the return wire.
  3. Round upIf you fall between rows or columns, use the higher current and the longer distance. A smaller AWG number means a thicker cable.

Good to know

  • Two limits, one answer. Each size keeps voltage drop to 3% and is at least what the cable is rated to carry (ABYC figures for 105°C-rated cable outside engine spaces). On short, high-current runs it is the current rating that decides.
  • Hot or crowded spaces. In an engine compartment, or bundled with other cables, go one size thicker.
  • 3% or 10%? 3% suits inverters, electronics, pumps and motors. Lighting can tolerate up to 10% — the inverter calculator works out any voltage drop.
  • Fuse the positive cable as close to the battery as you can, sized to protect the cable. See Class T fuses compared.